PVFE 24/24-12 |
PVFE 24/24-20 |
PVFE 24/24-24 |
PVFE 24/24-40 |
|
Input
|
Input rated voltage |
24 Vdc
|
24 Vdc
|
24 Vdc
|
24 Vdc
|
|
18 - 30 Vdc
|
18 - 30 Vdc
|
18 - 30 Vdc
|
18 - 30 Vdc
|
Input fuse internal |
2 x 15 A (slow‑blow)
|
2 x 15 A (slow‑blow)
|
4 x 15 A (slow‑blow)
|
4 x 15 A (slow‑blow)
|
Voltage drop per channel at rated load |
140 mVdc
|
240 mVdc
|
140 mVdc
|
240 mVdc
|
|
Output
|
Output rated voltage |
24 Vdc
|
24 Vdc
|
24 Vdc
|
24 Vdc
|
Resistance to reverse feed max. |
33 Vdc
|
33 Vdc
|
33 Vdc
|
33 Vdc
|
Number of current channels |
2
|
2
|
4
|
4
|
Output rated current |
2 x 1 ‑ 6 A (adjustable in 1 A steps)
|
2 x 1 ‑ 10 A (adjustable in 1 A steps)
|
4 x 1 ‑ 6 A (adjustable in 1 A steps)
|
4 x 1 ‑ 10 A (adjustable in 1 A steps)
|
Overload behaviour |
Shutdown without current limiting
|
Shutdown without current limiting
|
Shutdown without current limiting
|
Shutdown without current limiting
|
Parallel connection |
No
|
No
|
No
|
No
|
Turn on capacity |
max. 20.000 µF per channel
|
max. 20.000 µF per channel
|
max. 20.000 µF per channel
|
max. 20.000 µF per channel
|
Serial operation |
No
|
No
|
No
|
No
|
max. Power loss idling/nominal load |
2 / 4 W
|
2 / 7 W
|
2 / 5.5 W
|
2 / 12 W
|
Efficiency |
typ. 96 %
|
typ. 96 %
|
typ. 96 %
|
typ. 96 %
|
|
Signaling
|
Power Good (DC OK) |
LED green, LED red, LED yellow
|
LED green, LED red, LED yellow
|
LED green, LED red, LED yellow
|
LED green, LED red, LED yellow
|
Display, interface |
Yes, RS 232
|
Yes, RS 232
|
Yes, RS 232
|
Yes, RS 232
|
Reset input |
Yes, (18 - 30 Vdc)
|
Yes, (18 - 30 Vdc)
|
Yes, (18 - 30 Vdc)
|
Yes, (18 - 30 Vdc)
|
Active signal outputs |
4 x 24 Vdc, 1 configurable
|
4 x 24 Vdc, 1 configurable
|
4 x 24 Vdc, 1 configurable
|
4 x 24 Vdc, 1 configurable
|
Potential free signal contact |
Closing contact, configurable
|
Closing contact, configurable
|
Closing contact, configurable
|
Closing contact, configurable
|
|
Standards
|
Classification |
Electronic circuit breaker
|
Electronic circuit breaker
|
Electronic circuit breaker
|
Electronic circuit breaker
|
|
Approvals
|
Approvals |
cURus, cULus
|
cURus, cULus
|
cURus, cULus
|
cURus, cULus
|
|
Environment
|
Storage temperature |
-25° C to +85° C
|
-25° C to +85° C
|
-25° C to +85° C
|
-25° C to +85° C
|
Ambient temperature |
-10°C to + 60°C
|
-10°C to + 60°C
|
-10°C to + 60°C
|
-10°C to + 60°C
|
|
Safety and protection
|
|
IP 20
|
IP 20
|
IP 20
|
IP 20
|
Safety class |
III, without PE connection
|
III, without PE connection
|
III, without PE connection
|
III, without PE connection
|
|
Terminal and mounting
|
Connections input, (spring clamp terminal, pluggable) |
max. 10 mm²
|
max. 10 mm²
|
max. 10 mm²
|
max. 10 mm²
|
Connections output, (spring clamp terminal, pluggable) |
max. 2.5 mm²
|
max. 2.5 mm²
|
max. 2.5 mm²
|
max. 2.5 mm²
|
Connections signalling relay, reset (spring clamp terminal, pluggable) |
max. 2.5 mm²
|
max. 2.5 mm²
|
max. 2.5 mm²
|
max. 2.5 mm²
|
Connections signalling, (spring clamp terminal, pluggable) |
max. 0.5 mm²
|
max. 0.5 mm²
|
max. 0.5 mm²
|
max. 0.5 mm²
|
Mounting position |
vertical
|
vertical
|
vertical
|
vertical
|
Fixing method |
DIN Rail system TH 35
|
DIN Rail system TH 35
|
DIN Rail system TH 35
|
DIN Rail system TH 35
|
|
Measures and weights
|
Weight |
0.80 kg
|
0.80 kg
|
0.80 kg
|
0.80 kg
|
| |
Dimension Picture |
Dimension Picture |
Dimension Picture |
Dimension Picture |
|
Accessory
|
Connector for signalling |
PV-CON (optional)
|
PV-CON (optional)
|
PV-CON (optional)
|
PV-CON (optional)
|
Adapter cable for interface |
PV-KOK2 (optional)
|
PV-KOK2 (optional)
|
PV-KOK2 (optional)
|
PV-KOK2 (optional)
|
Side DIN Rail mounting |
PV-TS35M (optional)
|
PV-TS35M (optional)
|
PV-TS35M (optional)
|
PV-TS35M (optional)
|
Direct screw fastening plate for lateral mounting |
PV-WB2 (optional)
|
PV-WB2 (optional)
|
PV-WB2 (optional)
|
PV-WB2 (optional)
|
|
Order numbers
|
Order Number |
PVFE 24/24‑12
|
PVFE 24/24‑20
|
PVFE 24/24‑24
|
PVFE 24/24‑40
|