Input
|
Input rated voltage |
24 Vdc
|
|
|
|
|
18 - 30 Vdc
|
|
|
|
Input fuse internal |
4 x 15 A (slow‑blow)
|
|
|
|
Voltage drop per channel at rated load |
200 mVdc
|
|
|
|
|
Output
|
Output rated voltage |
24 Vdc
|
|
|
|
Number of current channels |
4
|
|
|
|
Output rated current |
1 ‑ 8 A (adjustable in 1 A steps)
|
|
|
|
Overload behaviour |
Shutdown with active current limiting
|
|
|
|
Parallel connection |
No
|
|
|
|
Turn on capacity |
typ. 20.000 µF
|
|
|
|
Serial operation |
No
|
|
|
|
max. Power loss idling/nominal load |
2 / 8.2 W
|
|
|
|
Efficiency |
typ. 96 %
|
|
|
|
|
Signalling
|
Power Good (DC OK) |
LED green, LED red, LED yellow
|
|
|
|
Potential free signal contact |
No
|
|
|
|
Display, interface |
Yes, RS 232
|
|
|
|
Reset input |
No
|
|
|
|
Feedback voltage max. |
33 Vdc
|
|
|
|
Active signal outputs |
4 x 24 Vdc, 2 configurable
|
|
|
|
|
Standards
|
Classification |
Electronic circuit breaker
|
|
|
|
|
Approvals
|
Approvals |
cURus, cULus
|
|
|
|
|
Environment
|
Ambient temperature |
-10° C to + 60° C
|
|
|
|
Storage temperature |
-25° C to +85° C
|
|
|
|
|
Safety and protection
|
|
IP 20
|
|
|
|
Safety class |
III, without PE connection
|
|
|
|
|
Accessory
|
Connector for signalling |
PV-CON (optional)
|
|
|
|
Adapter cable |
PV-KOK2 (optional)
|
|
|
|
Side DIN Rail mounting |
PV-TS35M (optional)
|
|
|
|
Direct screw fastening plate for lateral mounting |
PV-WB2 (optional)
|
|
|
|
|
Terminal and mounting
|
Connections input, (spring clamp terminal, pluggable) |
max. 10 mm²
|
|
|
|
Connections output, (spring clamp terminal, pluggable) |
max. 2.5 mm²
|
|
|
|
Connections signalling, (spring clamp terminal, pluggable) |
max. 0.5 mm²
|
|
|
|
Mounting position |
vertical
|
|
|
|
Fixing method |
DIN Rail system TH 35
|
|
|
|
|
Measures and weights
|
Weight |
0.80 kg
|
|
|
|
| |
Dimension Picture |
|
|
|
|
Order numbers
|
Order Number |
PVFB 24/24‑32
|
|
|
|